Description
Fire resistance:
EI 30–240
Seals: All types of
service penetrations
Premium: The best proforming
fire rated sealant
Tested: Causes no deleterious
effects on cPVC pipes
Sound reduction:
Rw 62 dB
Service life:
Minimum 30 years
(You need to be logged in to download some documents)

- Can be used alone or with Protecta FR Backing material, as specified in the installation manual
- Expands at approx. 180 °C to seal the opening in case of fire
- Seals most medium-sized pipes and cables
- Suitable for walls and floors made of gypsum, masonry, concrete, or cross-laminated timber
- Also tested for angled metallic pipes (90–45°)
Application properties:
- Recommended application temperature: +5 °C to +30 °C
- Surface skin formation (tack-free): Within 75 minutes
- Full cure time: in 3–5 days, depending on size and environmental conditions
Installation Video
Protecta FR Acrylic is a versatile firestop sealant designed to prevent the spread of fire, smoke, and toxic gases through joints and service penetrations in fire-rated walls and floors. It also helps maintain acoustic performance and airtightness within the building envelope.
This water-based sealant cures on exposure to air, forming a durable and slightly flexible joint capable of accommodating minor structural movement over time. In the event of a fire, FR Acrylic intumesces—expanding at approximately 180 °C, to create a robust barrier that effectively blocks flames and smoke.
Typical Applications
- Sealing around pipes and cables in walls and floors
- Firestopping perimeter gaps and linear joints
- Ideal for hospitals, schools, apartments, offices, and other commercial or residential buildings
FR Acrylic can be applied directly or used in combination with a suitable backing material to ensure correct joint depth and minimise shrinkage during curing. Depending on the application and dimensions, it provides up to 4 hours of documented fire resistance.

What types of pipes and cables are approved with FR Acrylic?
- Cables and conduits
- Steel pipes
- Copper pipes
- Alupex pipes
- PVC, PE, and PP plastic pipes
- PEX-in-PEX systems
See installation instructions for details and dimensions.
In which types of constructions has FR Acrylic been tested?
Protecta FR Acrylic has been fire tested in the following types of constructions:
- Concrete and masonry walls
- Drywall partitions
- Solid timber (CLT) walls
- Floor constructions made of concrete, masonry, and CLT
What fire resistance does Protecta FR Acrylic achieve?
From EI 30 to EI 240, depending on the type of service penetration, dimensions, insulation, joint size, and type of construction. For detailed approvals, please refer to the installation guidelines.
Can FR Acrylic be used around multiple pipes in one opening?
What is the minimum joint width?
Can FR Acrylic be used in damp areas?
Protecta FR Acrylic has European Technical Assessments – ETA 23/0257 and ETA 22/0735 – issued under EU Regulation 305/2011, based on EAD 350454-00-1104 and EAD 350141-00-1106.
The product is tested according to EN 1366-3, -4, and -12, with reference to EN 1363-1.
All Protecta products are proudly developed and manufactured by Polyseam Ltd. To meet the demanding standards of modern construction, we continuously invest in rigorous testing and development in collaboration with leading laboratories.

FR Acrylic is water-based with documented low environmental impact and long service life.
- Minimum 30-year service life – reduces waste and replacements
- Installation without hazardous chemicals
- Suitable for environmental building projects – meets BREEAM 6.0
- Environmental Product Declarations (EPDs) available – covers the full lifecycle from raw material to disposal

Useful Links
Here are some quick links to guide you through your fire protection journey with Protecta